Mitsubishi fixed speed rotary PE36NPBMT Compressors

Mitsubishi fixed speed rotary PE36NPBMT Compressors

Mitsubishi Rotary PE36NPBMT

Fixed Speed Rotary Compressors

Inverter-driven system promotes maximum compressor efficiency. The system detects subtle temperature changes and automatically adjust its capacity output. These lead to stabilizing temperature, minimizing power consumption and optimizing humidity control.

60Hz 208-230V 1P

R-407C Fixed Speed Rotary Compressor


Models Capacity Input Norminal Output COP EER Run Cap Weight Oil
W Kcl/hr Btu/hr Watt Amps HP kW W/W Btu/hr* w mF/VAC kgs cc
PE36NPBMT 7427 6386 25341 2400 11.30 2.1 1.60 3.09 10.56 35/370 22.7 900

Operation Standards R-407C Fixed speed rotary compressor

Model RE Series PE Series NE Series
Compressor
Type Rolling piston type rotary
Displacement (mc3/rev) 13.5-31.3 28.1-41.7 28.0-56.9
Refrigerant type R-407C
Pressure
Maximum Condensing 1.10 MPaG ~2.83 MPaG (159.5 psiG - 410.4 psiG)
Evaporating 0.26 MPaG ~0.73 MPaG (37.7 psiG - 105.9 psiG)
Compression Ratio 6 or less 8 or less
Abnormal rise in pressure 4.9 MPaG (710.6psiG) or less
Temprature
Condensing 28°C ~ 65°C
Evaporating -10°C ~ 15°C
Discharged gas max 120°C (248°F)
In case of heat pump or de-humidipier, this limit is 110°C (230°F)
Suction gas max must be over 0°C (No liquid back)
Discharged gas superheat 20°C or more
Outdoor ambient temp Air cond : 20°C~43°C (68°F~109.4°F)
Heat pump: -10°C~43°C(14°F~109.4F)
Electrical
Supply voltage (during operation) Rated voltage + or - 10%
Starting voltage Maximum 80% of rated voltage
(at 1.01 MPa balancing pressure in case of 208-230 v Rated voltage (N code compressor) the starting voltage shall be 85% or more . This shall be measured at compressor terminal at instance of start.)
Reverse phase (rotation) Compressor is not designed to run reverse phase
Frequency range Rated frequency + or - 2%
ON/OFF
ON/OFF Frequency Less than 170000 cycles
ON/OFF Cycle The ON/OFF cycle shall be amximum of 10 times/hr
OFF time shall be the time until the high side and low side pressure reach to balance pressure (more than 3 minuts)
Pipe Stress 3.5Kg/mm2 or less at start and stom conditions
(1.8 kg/mm2 during operation)
Refrigerant Circuit
Piping Vibration Maximum 0.8mm
Inclination of compressor Within 5°